energy_methods.data_center_wind#
Annual wind procurement and hourly-matching screens for electricity buyers.
Annual energy matching is not evidence of 24/7 hourly clean supply. The hourly method consumes explicit profiles and reuses hybrid_dispatch.
- class energy_methods.data_center_wind.AnnualWindScreen(target_twh, required_wind_gw, annual_delivered_twh)[source]#
Bases:
objectRequired GW and annual delivered TWh for an annual energy target.
- Parameters:
target_twh (float)
required_wind_gw (float)
annual_delivered_twh (float)
- target_twh: float#
- required_wind_gw: float#
- annual_delivered_twh: float#
- class energy_methods.data_center_wind.HourlyWindScreen(energy_matched_fraction, hourly_served_fraction, delivered_wind_mwh, demand_mwh, curtailed_mwh, unmet_mwh)[source]#
Bases:
objectFinite sample-window energy and temporal coverage, not grid availability.
- Parameters:
energy_matched_fraction (float)
hourly_served_fraction (float)
delivered_wind_mwh (float)
demand_mwh (float)
curtailed_mwh (float)
unmet_mwh (float)
- energy_matched_fraction: float#
- hourly_served_fraction: float#
- delivered_wind_mwh: float#
- demand_mwh: float#
- curtailed_mwh: float#
- unmet_mwh: float#
- energy_methods.data_center_wind.screen_annual_wind(demand_twh, target_fraction, capacity_factor, delivery_loss_fraction=0.0, *, hours_per_year=8760)[source]#
Size nameplate GW to equal a fraction of demand on an annual MWh basis.
Assumes constant net capacity factor and constant delivery losses; excludes congestion, interconnection queues, profile correlation, PPA settlement, construction lead times and additionality. A target fraction of zero gives zero capacity. Does not make a firm-power or hourly-matching claim.
- Parameters:
demand_twh (float)
target_fraction (float)
capacity_factor (float)
delivery_loss_fraction (float)
hours_per_year (int)
- Return type:
- energy_methods.data_center_wind.screen_hourly_wind(wind_cf, demand_mw, *, wind_capacity_mw, delivery_loss_fraction=0.0, battery_power_mw=0.0, battery_energy_mwh=0.0, battery_round_trip_efficiency=0.9, timestep_hours=1.0)[source]#
Contrast total-window MWh matching with physical hourly served share.
wind_cf is an explicit site/profile-level fraction in [0, 1]. Storage starts empty, may charge only from excess wind, and does not import grid electricity. Greedy dispatch does not optimize economics. Energy matching assumes all generated MWh can be credited over the same window, even if it is spilled at the load site; it is a deliberately permissive contract accounting ceiling, not a certified procurement or dispatch claim.
- Parameters:
wind_cf (Sequence[float])
demand_mw (Sequence[float])
wind_capacity_mw (float)
delivery_loss_fraction (float)
battery_power_mw (float)
battery_energy_mwh (float)
battery_round_trip_efficiency (float)
timestep_hours (float)
- Return type: