Portugal’s 1,050 MVA grid-storage tenders: battery sizing pre-screen#

News (9 November 2026): Portugal offered 750 MVA of standalone BESS grid access and 300 MVA of renewable-plus-BESS grid access, with applications reported due 22 December 2026. MVA is apparent-power access, not installed battery MW, actual dispatch or MWh generation.

Business question: What conditional inverter power and nameplate storage energy would be required for candidate bids, including end-of-life allowance?

Evidence: Portuguese DGEG tender orders 12924-B/2026 and 12924-C/2026, government announcement (27 October), and pv magazine España (9 November). The source-level evidence record separates dated reported facts from illustrative engineering assumptions. See technical guide.

Not legal compliance: DGEG’s co-located wording refers to four hours at maximum injection power. The battery-rated-power calculation below is a preliminary 20%-inverter stress only, compared against a stricter full injection stress. Neither substitutes for the controlling tender documents.

  1. Audit external evidence and keep modeled inputs separate from facts.

import json
from pathlib import Path

import matplotlib.pyplot as plt

from energy_methods.portugal_storage_auction import (
    AUCTION_CAPACITY_MVA,
    MINIMUM_BID_MVA,
    StorageAuctionScenario,
    screen_portugal_storage_auction,
)

script_path = Path(globals().get("__file__", Path.cwd() / "plot_portugal_storage_auction_2026.py"))
evidence = json.loads(
    (script_path.resolve().parent / "portugal_storage_auction_2026.json").read_text(
        encoding="utf-8"
    )
)
sources = {row["source_id"]: row for row in evidence["reported_evidence"]}
assumed = evidence["illustrative_assumptions_NOT_OBSERVED"]
assert sources["dgeg_standalone"]["capacity_mva"] == AUCTION_CAPACITY_MVA["standalone"]
assert sources["dgeg_colocated"]["capacity_mva"] == AUCTION_CAPACITY_MVA["colocated"]
assert sources["pv_magazine_nov9"]["minimum_bid_mva"] == MINIMUM_BID_MVA
print("Official offered connection pools: 750 MVA standalone + 300 MVA co-located")
print("SCENARIO values below are not observed Portuguese battery installations.")
Official offered connection pools: 750 MVA standalone + 300 MVA co-located
SCENARIO values below are not observed Portuguese battery installations.
  1. Size nameplate sensitivity for hypothetical MVA candidates.

bid_mva = assumed["bid_mva"]
categories = ("standalone", "colocated")
screened = {
    category: [
        screen_portugal_storage_auction(
            StorageAuctionScenario(
                category,
                value,
                ac_discharge_efficiency=assumed["ac_discharge_efficiency"],
                end_of_life_usable_fraction=assumed["end_of_life_usable_fraction"],
            )
        )
        for value in bid_mva
    ]
    for category in categories
}
for category, results in screened.items():
    for result in results:
        print(
            f"{category:10} {result.awarded_capacity_mva:.0f} MVA: "
            f"{result.minimum_bess_ac_mw:.0f} MW inverter screen, "
            f"{result.minimum_nameplate_mwh:.1f} MWh assumed nominal, "
            f"{result.full_export_four_hour_nameplate_mwh:.1f} MWh full-export stress"
        )
fig, ax = plt.subplots(figsize=(8.8, 4.6), layout="constrained")
for category, results in screened.items():
    ax.plot(
        bid_mva,
        [result.minimum_nameplate_mwh for result in results],
        marker="o",
        label=f"{category}: 4 h at BESS power",
    )
ax.plot(
    bid_mva,
    [result.full_export_four_hour_nameplate_mwh for result in screened["colocated"]],
    linestyle="--",
    color="black",
    label="co-located: 4 h full-injection stress",
)
ax.set(
    xlabel="Candidate injection access (MVA; NOT MW)",
    ylabel="Illustrative nominal battery energy (MWh)",
    title="Portugal tenders: separate four-hour design interpretations",
)
ax.legend()
plt.show()
Portugal tenders: separate four-hour design interpretations
standalone 50 MVA: 50 MW inverter screen, 266.0 MWh assumed nominal, 266.0 MWh full-export stress
standalone 100 MVA: 100 MW inverter screen, 531.9 MWh assumed nominal, 531.9 MWh full-export stress
standalone 200 MVA: 200 MW inverter screen, 1063.8 MWh assumed nominal, 1063.8 MWh full-export stress
colocated  50 MVA: 10 MW inverter screen, 53.2 MWh assumed nominal, 266.0 MWh full-export stress
colocated  100 MVA: 20 MW inverter screen, 106.4 MWh assumed nominal, 531.9 MWh full-export stress
colocated  200 MVA: 40 MW inverter screen, 212.8 MWh assumed nominal, 1063.8 MWh full-export stress
  1. Unit and loss sensitivity: MVA cannot silently be treated as MW.

pfs = assumed["active_power_factor"]
fig, ax = plt.subplots(figsize=(8.8, 4.6), layout="constrained")
for category in categories:
    answers = [
        screen_portugal_storage_auction(
            StorageAuctionScenario(
                category,
                50,
                active_power_factor=pf,
                ac_discharge_efficiency=assumed["ac_discharge_efficiency"],
                end_of_life_usable_fraction=assumed["end_of_life_usable_fraction"],
            )
        )
        for pf in pfs
    ]
    ax.plot(
        pfs,
        [result.minimum_nameplate_mwh for result in answers],
        marker="o",
        label=f"{category} screen",
    )
ax.set(
    xlabel="Assumed active power factor (MW/MVA)",
    ylabel="Conditional nameplate battery capacity (MWh)",
    title="50 MVA bid: hypothetical power-factor sensitivity",
)
ax.legend()
plt.show()
50 MVA bid: hypothetical power-factor sensitivity

Interpretation: no individual node availability, license eligibility, PPA, battery dispatch measurements, market revenues, deposits or costs are known. Reproduce: uv run –no-sync python examples/analysis/plot_portugal_storage_auction_2026.py

Total running time of the script: (0 minutes 0.165 seconds)

Gallery generated by Sphinx-Gallery